Introduction

APC Metered Rack Power Distribution Units (PDUs) provide active metering to enable energy optimization and circuit protection. User-defined alarm thresholds mitigate risk with real-time local and remote alerts to warn of potential circuit overloads. Metered Rack PDUs provide power utilization data to allow Data Center Managers to make informed decisions on load balancing and right sizing IT environments to lower total cost of ownership. Metered Rack PDUs include real power monitoring, a temperature/humidity sensor port, locking IEC receptacles, and ultra low profile circuit breakers. Users can access and configure Metered Rack PDUs through secure Web, SNMP, or Telnet Interfaces which are complimented by APC Centralized Management platforms using InfraStruxure Central, Operations, Capacity, and Energy Efficiency.

Design

PDU types

Metered

Rack capacity

0U

Mounting

Horizontal/Vertical

Product colour

Black

Display

LCD

Ports & interfaces

AC outlets quantity

42 AC outlet(s)

AC outlet types

C13 coupler, C19 coupler

Input connection type

IEC 309 30A 3P+N+E

Features

Cable length

1.83 m

Certification

cUL, EN 55022 A, EN 55024, EN 61000-3-2, EN 61000-3-3, FCC-15 A, UL, VCCI A

Power

Nominal input voltage

400 V

AC input frequency

50 - 60 Hz

Maximum current

30 A

Nominal output voltage

240 V

Output voltage

240 V

Load capacity

17300 VA

Maximum input current per phase

30 A

Maximum total current draw per phase

24 A

Power protection features

Overload

Weight & dimensions

Dimensions (WxDxH)

56 x 51 x 1829 mm

Weight

9.6 kg

Packaging data

Package dimensions (WxDxH)

221 x 112 x 2149 mm

Package weight

13.6 kg

Operational conditions

Operating temperature (T-T)

0 - 55 °C

Storage temperature (T-T)

-25 - 65 °C

Operating relative humidity (H-H)

5 - 95%

Storage relative humidity (H-H)

5 - 95%

Operating altitude

0 - 3000 m

Non-operating altitude

0 - 15000 m

Technical details

Sustainability certificates

RoHS